The Honeywell R7849A1015 0.8 OR 1 SEC Flame FAILURE RESPONSE TIME.
Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
Comments |
Color: Purple |
Approvals, Underwriters Laboratories Inc. |
Listed: File No. MP268, Guide No. MCCZ |
Approvals, Canadian Standards Association |
Certified: File No. LR95329-3 |
Flame Failure Response Time (sec) |
8 sec or 1.0 sec |
Approvals, Swiss RE |
Acceptable |
Approvals, Factory Mutual |
Approved: Report No. 1V9A0.AF |
Weight (g) |
71g |
Self Checking |
None (standard) |
Use With Primary Safety Control |
7800 SERIES Relay Modules |
Use With Flame Sensor |
Gas, Oil: Minipeeper C7027A, C7035A, C7044 |