The Fireye EP100S Programmer. Selectable purge, selectable TFI, non-recycle, Spanish language.
The Fireye EP Programmer Modules are used with the Flame-Monitor Burner Management Control System (P/N’s E110 and E100). They provide start-up programming, safe start check, and flame monitoring supervision. They insure open damper high fire purge interlock (EP100 series only), proof of low fire position and fuel valve end switch safety checks. A running interlock circuit on the Flame-Monitor system constantly monitors the limit switches, air flow switches, and fuel pressure switches through the programmer. The EP programmer modules will de-energize all fuel valve circuits with 4 seconds (max.) following a flame failure (2 seconds for the EP165, EP166, EP265), or at the end of the pilot-trial-for-ignition period if no flame is detected. A modulator (firing rate motor) circuit is provided on the EP100 andEP200 series programmers. The EP300 series programmers do not provide a modulator circuit. The EP programmers provide a Check-Run switch to stop the control in its firing sequence at any time (except MTFI) to aid in set-up, start-up, and check out of the burner and its associated interlocks.