**Obsoleted… please call Apex at 610-344-9156 for alternatives
The Honeywell R7795A1001 120 V 50/60 HZ. 120 Vac Primary Controls with 3 sec flame failure response time and 10 to 15 second safety switch timing.
Provides solid state, electronic flame safeguard protection for commercial and industrial single or dual fuel burners
Include flame signal amplifiers that are color-coded: purple for ultraviolet and green for rectification.
Require a plug-in prepurge timer of 1.5, 7, 10, 30, 60, or 90 seconds.
Mount on a Q795A Wiring subbase with two captive screws.
Include line voltage airflow switch to prove airflow from the start of prepurge through the run period.
Prevent start-up with lockout if flame or a flame simulating failure exists.
Require a plug-in prepurge timer of 1.5, 7, 10, 30, 60, or 90 seconds.
Mount on a Q795A Wiring subbase with two captive screws.
Include line voltage airflow switch to prove airflow from the start of prepurge through the run period.
Prevent start-up with lockout if flame or a flame simulating failure exists.