- Jumper-selectable control range (0-20 psig or 3-15 psig)
- Field-selectable inputs ( 0-5 VDC, 0-10 VDC, 4-20 mA)
- LCD display for local indication of readings
- No air consumption and quiet operation
- Easy mounting with snap track housing
- Optional pressure loss alarm
Specifications
Supply Voltage:24 VAC/VDC
Supply VA:150 mA maximum (half-wave)
Input:0-5 VDC, 0-10 VDC, or 4-20 mA
Input Impedance:10 kΩ, VDC input; 250 Ω, 4-20 mA input
Output:0-20 psig (0-140 kPa) or 3-15 psig (21-103 kPa)
Wiring Terminations:Screw terminals
Air Capacity:333 scim (5456 cm3/min) @ 20 psig (138 kPa) supply; 523 scim (8570 cm3/min) @ 45 psig (310 kPa) supply
Air Connections:Brass barbs for 1/4″ OD tubing
Air Consumption:None in steady state
Maximum Pressure:45 psig (310 kPa)
Media Compatibility:Clean dry air
Minimum Tubing Length:15 ft. (4.6 m)
Repeatability:<1% full scale
Linearity:<1% full scale
Hysteresis:<1% full scale
Operating Temperature:25° to 140℉ (-4° to 60℃)
Operating Humidity:10 to 90% RH (non-condensing)