The Veris EP2100S EP,Analog In,3-15/0-20psi
SPECIFICATIONS
Application Zone | : | Plant Room |
Application | : | Pneumatic Actuated Dampers | Pneumatic Actuators |
Brand | : | Veris |
Dimension Depth | : | 1.8″ (46 mm) |
Dimension Height | : | 3.5″ (89 mm) |
Dimension Width | : | 3.3″ (84 mm) |
Display Type | : | None |
Electrical Wiring | : | 3-wires |
Fail Safe | : | None |
Fitting Material | : | Brass |
Fitting Size | : | 0.18″ (4.3 mm) |
Fitting Type | : | Male |
Input Specifications | : | 4 – 20 mA | 0 – 5 V | 0 – 10 V |
LED Indicator Type | : | Red and Green |
Measurement Type | : | Electropneumatic Transducers |
Medium | : | Dry Air | Inert Gas |
Model | : | EP2100S |
Mounting | : | Panel |
Operating Humidity | : | 10 – 90% RH, non-condensing |
Operating Temperature | : | 25 – 140 °F (-4 – 60 °C) |
Output Specifications | : | None |
Pressure Measurement Accuracy | : | ±1% of F.S. |
Pressure Measurement Range | : | 3 – 15 psi (0.2 – 1 bar) | 0 – 20 psi (0 – 1.35 bar) |
Product Type | : | Sensor |
Range | : | EP2 |
Standards EMC | : | EN 61000-6-3:2007 | A1:2011 Class B | EN 61000-6-1:2007 |
Supply Voltage AC Nominal | : | 24 VAC |
Supply Voltage AC Range | : | 24 – 30 VAC |
Supply Voltage DC Nominal | : | 24 VDC |
Warranty | : | 5 years |
FEATURES
The EP2 series electro pneumatic pressure transducer uses microcontrolled poppet valve technology for highly accurate pressure sensing in multiple applications. The poppet valves consume no air, eliminating unnecessary air losses in the system and allowing for stable and reliable operation. The EP2 comes installed on standard SnapTrack. An LCD display and LED indicators make it easy to read system status at a glance.
- Field-selectable 4 to 20 mA/0 to 5 V/0 to 10 VDC input for application flexibility
- Poppet valve technology for quiet operation
- Manual override with set and hold feature, great for commissioning leaky systems
- Media connection – clean, dry air, or inert gas, do not use with oxygen service
- Pressure indication – electronic, 3-1/2 digit LCD