The Honeywell M9185D1004 Actuator replaces M945A1157 & A1024, Spring Return Foot Mounted, 60LB-IN., 160 DEG ADJ Stroke, 24 VOLTS 30-60 SEC Timing.
Series 90 Modutrol Motors by Honeywell such as the M9185D1004 actuator are spring return modulating proportional control motors used with controllers that provide a Series 90 output to operate dampers or valves.
Integral junction box provides NEMA 3 weather protection.
Integral spring return returns motor to normal position when power is interrupted.
Motor and circuitry operate from 24 Vac.
Quick-connect terminals are standard-screw terminal adapter is available.
Adapter bracket for matching shaft height of older motors is available.
Motors have field adjustable stroke (90A to 160A).
Integral auxiliary switches are available factory mounted, or can be field added.
Spring return motors can operate valve linkages from power end or normally open valve applications.
All models have dual shafts (slotted and tapped on both ends).
All models have auxiliary switch cams.
Fixed torque throughout the entire voltage range.
Product Specifications
Application | Electric |
Dimensions (in.) | 6 7/16 in. high x 5 1/2 in. wide x 8 3/4 in. deep |
Dimensions (mm) | 164 mm high x 140 mm wide x 222 mm deep |
Weight (lb) | 8.5 lb |
Item Type | Product |
Mounting | Foot-mounted |
Frequency | 50 Hz; 60 Hz |
Approvals, Underwriters Laboratories Inc. | Listed: File No. E4436, Guide No. XAPX for USA and Canada |
Tradeline Value | Tradeline |
Electrical Connections | Quick-connect terminals |
Supply Voltage | 24V |
Power Consumption | Driving– 20 VA |
Approvals, CE | EN55011 (Emission) EN50082-2 (Immunity) 73/23/EEC (LVD) |
Ambient Temperature Range (F) | -40 F to +150 F |
Ambient Temperature Range (C) | -40 C to +60 C |
Internal Auxiliary Switch | 0 |
Auxiliary Switch Ratings | AFL – 120 Vac– 7.2A; ALR- 120 Vac– 43.2A; AFL – 240 Vac– 3.6A; ALR- 240 Vac– 21.6A |
Stroke | Adjustable; 90 to 160 degrees, Asymmetrical |
Shaft Dimensions (in.) | 0.375 in. Square |
Control Signal | Proportional, 135 ohm |
Fail Safe Mode | Spring Return |
Torque Rating (lb-in.) | 60 lb-in. |
Torque Rating (Nm) | 6.8 Nm |
External Auxiliary Switches Available | Yes |
Shaft Rotation (upon control signal increase) | Clockwise (as viewed from power end) (normally closed) |
Factory Stroke Setting | 160 degrees |
Timing, Nominal | 30-60 sec |
Feedback | No |
Shaft Dimensions (mm) | 10 mm Square |
Motor shafts | Dual-ended shaft |
Deadweight Load on Shaft | Either End– 200 lbs.; Combined on both Shafts– 300 lbs. |
Internal Transformer | None |