The Fireye MP561 Programmer, Selectable recycle/non-recycle function, TFI, and purge timing. Pilot cutoff, check-run switch.
The Fireye MP561 Programmer Module is used with the Fireye Modular M-Series II control. The operational characteristics of the control are determined by the selection of the programmer module (e.g. re-ignition, 2-stage capability, pilot cutoff, etc.). The programmer module incorporates a plug-in design for easy installation. Some programmer modules (MP230, MP230H, MP560, MP561, and MP562) are equipped with a series of dipswitches to select Purge Timing. Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation. LED indicator lights are on all programmer modules, indicating the operating status of the control. A “check-run” switch is provided on the MP560, MP561 and MP562 programmer modules to assist in testing size and stabilization of the pilot. Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module. Test jacks are also provided on the flame amplifier module to permit flame signal measurement during operation. For proper and safe application of this product, you must refer to Fireye bulletin C-4000 or C-4000E for a detailed description of the various programmer modules, including installation instructions, amplifier selection, operating sequences for each programmer module, etc.
Apex Controls is not affiliated with Fireye or the use of the Fireye logo