The Honeywell R7848B1006 Flame Amplifier 3S FFRT. RECOMMENDED FOR BurnerS SHUT DOWN AT LEAST DAILY. USE WITH C7015 LEAD SULFIDE Sensor; Flame Signal Amplifier, 2 Second or 3 Second Flame Failure Response Time, Ampli-Check, Gas,Oil, Coal: Infrared ( Lead Sulfide ) Flame Sensor C7015, Use with 7800 Series Primary Safety Control, Color: Red, Flame Signal Strength Ranges from 0.0-5 Vdc
The R7848A,B Infrared Flame Amplifiers are solid state plug-in amplifiers that respond to an infrared signal from a C7015 Infrared Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
Comments |
Color: Red |
Approvals, Underwriters Laboratories Inc. |
Listed: File No. MP268, Guide No. MCCZ |
Approvals, Canadian Standards Association |
Certified: File No. LR95329-3 |
Flame Failure Response Time (sec) |
2.0 sec or 3.0 sec |
Approvals, Swiss RE |
Acceptable |
Approvals, Factory Mutual |
Approved: Report No. 1V9A0.AF |
Self Checking |
Ampli-Check |
Use With Primary Safety Control |
7800 SERIES Relay Modules |
Use With Flame Sensor |
Gas, oil, coal: Infrared ( lead sulfide) C7015 |