The Honeywell V4062A1131 actuator for gas valves.
Overview
Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand.
Features
- Provide final safety shutoff service when used with V5055 or V5097 gas valve.
- One-second maximum closing time.
- Continuously displays the valve position with a red indicator when open and a yellow indicator when closed.
- Mount in any position directly to valve bonnet with three setscrews.
- Provide final safety shutoff service when used with V5055 or V5097 Gas Valves.
Product Specifications
- Maximum Safe Operating Pressure (psi)
- 5 psi
- Maximum Safe Operating Pressure (kPa)
- 34 kPa
- Temperature Range (F)
- -40 F to +150 F
- Temperature Range (C)
- -40 C to +66 C
- Includes
- Damper Shaft
- Used With
- V5034; V5055; V5097; VE5000
- Electrical Ratings
- 120 Vac
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ
- Approvals, Canadian Standards Association
- When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada
- Approvals, Swiss RE
- When used with V5055 or V5097: Acceptable
- Timing
- Opening– 13 sec; Closing– < 1 sec
- Internal Auxiliary Switch
- No