The Honeywell V5055A1038 2 in. NPT Industrial Gas Valve with On-off safety shut-off.
Overview
Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners.
Features
- Use with natural or LP gases.
- Mount directly in gas supply line.
- Include 1/4 in. NPT upstream and downstream taps and plug.
- 4 in. models have only flanged connections.
- V5055 normally closed valves are rated for final shutoff service safety shutoff.
- V5055A,C,D,E Valves are for On-Off service.
- V5055B Valve has a characterized guide and in combination with the V4055, V4062, and V9055 Fluid Power Actuators, provides slow-opening, hi-lo-off, and modulating functions respectively.
- V5055C,E,F Valves have a double seal and are used with V4055D,E Actuators to provide proof-of-closure switch and valve seal over-travel interlock.
- V5055D,E,F Valves are for high pressure applications.
Product Specifications
Includes | 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug |
Used With | V9055; V4055; V4062 |
Item Type | Product |
Approvals, Underwriters Laboratories Inc. | When used with V4055A,B,D,E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ |
Approvals, Canadian Standards Association | When used with V4055, V4062, and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada |
Operating Temperature Range (F) | -40 F to +150 F; When used with V9055– -40 F to +125 F |
Operating Temperature Range (C) | -40 C to +66 C; When used with V9055– -40 C to +52 C |
Approvals, Swiss RE | When used with V4055A,B,D,E, V4062, V9055: Acceptable |
Approvals, Factory Mutual | When used with the V4055A,G: Approved, Report Nos. 20698, 20835, 21172, and 24061 |
Connection Type | NPT |
Capacity (m³/hr) | 102.5 m3/hr |
Pipe Size (inch) | 2 in. |
Pipe Size (DN) | DN50 |
Capacity (cfh) | 3620 cfh |
Maximum Operating Differential Pressure | With V4055A,D or V4062– 5 psi (340 mbar); With V4055B or E– 15 psi (1 bar) |