Split-Core Current Transducer for SZW244
Features: 0.333V Output Secondary, Unique low voltage output allows safe opening of transformer secondary, protecting installers from shock hazards found on traditional 5A CTs. Eliminates Need for “Shorting Blocks”. Standard. Split-core Enclosure Design. Snap close package speeds installation and eases retrofits for existing jobs. Eliminates need to power down or disconnect system to install CT, maximizing up time. High-Impact, UL94 V0 Rated Polymer Housing. No exposed metal parts on assembled devices SPECIFICATIONS: • Power Required o None—Self-powered • Accuracy o 0.5% FS, +/- 2% CTP • Output o 0–0.333V • Phase Angle o <1 degree., 2 degrees @ 50% • Range Response Time o <1 ms • Isolation Voltage o 600VAC • Max. Primary Voltage o 5000VAC (insulated conductor) • Max Inrush Current o 300% Full Scale Range (6 sec. duration) • Environmental o -0 to 122oF (-18 to 50oC), 0-95% • RH noncondensing