Installation Guide (2-Way Butterfly Valves)
Installation Guide (3-Way Butterfly Valves)
Specifications
- Actuator Type
- Non fail-safe
- Auxiliary Switches
- 2 SPDT
- Application
- Water
- Control Type
- Floating/3-point
- Degree of Protection
- IP66/67
- NEMA 4X
- UL Enclosure Type 4X
- Electrical Connection
- Terminals
- Manual Override
- 7 mm hex crank
- supplied
- Power Consumption (Running)
- 20 W
- Product Type
- Actuator
- Protection category
- IP66/67
- Running Time (Motor)
- 35 s
- Voltage AC/DC
- AC 24…240 V / DC 24…125 V
Application
PR Series valve actuators are designed with an integrated linkage and visual position indicators. For outdoor applications, the installed valve must be mounted with the actuator at or above horizontal. For indoor applications the actuator can be in any location including directly under the valve.
Operation
The PR series actuator provides 90° of rotation and a visual indicator shows the position of the valve. The PR Series actuator uses a low power consumption brushless DC motor and is electronically protected against overload. A universal power supply is furnished to connect supply voltage in the range of AC 24…240 V and DC 24…125 V. Included is a smart heater with thermostat to eliminate condensation. Two auxiliary switches are provided; one set at 10° open and the other is field adjustable. Running time is field adjustable from 30…120 seconds by using the Near Field Communication (NFC) app and a smart phone.
†Use 60°C/75°C copper wire size range 12…28 AWG, stranded or solid. Use flexible metal conduit. Push the listed conduit fitting device over the actuator’s cable to butt against the enclosure. Screw in conduit connector. Jacket the actuators input wiring with listed flexible conduit. Properly terminate the conduit in a suitable junction box. Rated impulse Voltage 4000 V. Type of action 1. Control pollution degree 3.
Reviews